Frame size 112
Housing material Aluminum
Install model According to the standard
Type of feet Removable feet
Net weight 24.5 kg
Insulation class F H (Standard) (Optional)
Protection degree IP 55IP 56 (Standard)(Optional)
Thermal protection WithoutCustomizable(Standard)(Optional)
Rotation direction ClockwiseCounter clockwise(Standard)(Optional)
Service duty S1
Vibration level A
Balance Half-key balanced
Cable glands 2 - M25 × 1.5
Cooling IC 411
Painting color RAL 7024Customizable(Standard)(Optional)
Regulations IEC / DIN / ISO / VDE / EN
Standard IEC 60034
Ambient temperature From -20°C to +40°C
Maximum altitute 1000 m above sea level
 
Output 2.2 kW
Frequency 50Hz
Voltage (±5%) 230V Δ @ 50Hz
400V Y @ 50Hz
276V Δ @ 60Hz
480V Y @ 60Hz
Rotation speed 945RPM @ 50Hz
1135RPM @ 60Hz
Rated current 10.1A (In) @ Δ 50Hz
5.80A (In) @ Y 50Hz
Starting current 4.8 ×In
Rated torque 22.23 Nm (Mn)
Starting torque 1.9 ×Mn
Breakdown torque 2.3 ×Mn
Efficiency

IE1

79.3
79.5
76.5
@ 100% load
@ 75% load
@ 50% load
Power factor cosφ 0.69 @ 100% load
Bearings brand C&U Customizable(Standard)(Optional)
Bearings type 6306 2RZ C3
6206 2RZ C3
(DE)
(NDE)
Grease type
Moment of inertia 0.01395 Kg*m²
Noise level 64 dB(A)
Drawings Test reports Print